为什么不能用NI系统配置API来重启装有WES7的TPC/CompactRIO/CompactDAQ



主要软件: LabVIEW Development Systems>>LabVIEW Professional Development System
主要软件版本: 2015
主要软件修正版本: N/A
次要软件: N/A
硬件: Industrial Communications>>HMI and Industrial PC>>Touch Panel Computers>>Touch Panel Computer with WES7>>TPC-2230, Industrial Communications>>HMI and Industrial PC>>Touch Panel Computers>>Touch Panel Computer with WES7>>TPC-2212, Industrial Communications>>HMI and Industrial PC>>Touch Panel Computers>>Touch Panel Computer with WES7>>TPC-2206, Industrial Communications>>HMI and Industrial PC>>Touch Panel Computers>>Touch Panel Computer with WES7>>TPC-2215

问题:

我在使用运行Windows嵌入式操作系统的TPC。当我使用使用以下方法来,系统配置API来重启目标设备的时候,LabVIEW返回错误。

1 根据下图的框图,我使用初始化VI和重启VI对目标进行初始化和重启。

 

LabVIEW返回错误:System Configuration: (Hex 0x80040378) The NI System Configuration API is not installed at the specified target.

2 我用以下的框图初始化和重启目标

 

LabVIEW返回错误:NI System Configuration: (Hex 0x80040474) Command is not supported by given protocol.LabVIEW Remote Development Target Support 在目标设备上已经安装并使能。我验证过IP地址是正确的,为什么不能用这些方法来重启?



解答:

你必须使能该设备的远程系统配置。默认地,系统配置中只有本地系统被使能。默认的设置确保了系统的安全,直到你修改设置。

使能远程的进入,完成以下的步骤:

1 打开MAX,在配置目录中,选择我的系统。

2 在系统设置部分,系统配置网页中年下拉选择本地和远程。



相关链接: KnowledgeBase 6LR8GEQY: NI LabVIEW 2014 Remote Development Target Support Readme

附件:





报告日期: 06/04/2015
最近更新: 11/04/2015
文档编号: 6Y3ERCQY