From Friday, April 19th (11:00 PM CDT) through Saturday, April 20th (2:00 PM CDT), 2024, ni.com will undergo system upgrades that may result in temporary service interruption.

We appreciate your patience as we improve our online experience.



當我在使用NI硬體的時候,為什麼會跳出錯誤碼-200152或-200175呢?



主要軟體:
主要軟體版本: 4.5
主要軟體修正版本: N/A
次要軟體: N/A
硬體: SCXI

問題: 當我在使用NI硬體的時候,會出現以下兩種錯誤訊息:

Error -200152: Data read from the EEPROM on the device is invalid.

Verify that any accessories configured with this device are connected. If the problem continues, contact National Instruments Technical Support. The device might need to be recalibrated or repaired by NI




Error -200175: Hardware is not responding.

Ensure your hardware is powered on and all cables are properly connected.



我要如何解決這個問題?

解答: 裝置的EEPROM有可能會造這些錯誤。有可能發生在Measurement & Automation Explorer (MAX),或正在執行程式碼時。

對於不同的系統裝置,這邊有一些對應的解決方案:

SCXI System
  • 重置您的SCXI設定
    1. 在MAX內刪除您的SCXI裝置
    2. 將SCXI系統重新上電
    3. 重新配置您的裝置
  • 在MAX,對有問題的裝置按下Reset Device
  • 試著調換SCXI機箱內卡片的位置
PXI System
  • 重置您的PXI 設定
    1. 在MAX內刪除您的PXI裝置 
    2. 將PXI系統重新上電
    3. 重新配置您的裝置 
  • 在MAX,對有問題的裝置按下Reset Device
  • 試著調換PXI機箱內卡片的位置
cDAQ System
  • 重置您的cDAQ 設定
    1. 拔除cDAQ與電腦的連線
    2. 在MAX內刪除cDAQ的記錄
    3. 將cDAQ重新上電 
    4. 將cDAQ與電腦重新連線
  • 在MAX,對有問題的裝置按下Reset Device
  • 試著調換cDAQ機箱內卡片的位置
如果以上這些建議的方式都無法消除這個錯誤,那麼您的硬體裝置很有可能需要維修。需要進一步的協助,請與我們連絡,或參閱ni.com/support。


相關連結: Products and Services: Sensor Measurements and Signal Conditioning
KnowledgeBase 2U5E94FL: Troubleshooting an SCXI Chassis
KnowledgeBase 59HAAEHN: Network cDAQ Troubleshooting Resources

附加檔案:





報告日期: 01/05/2009
最後更新: 04/01/2015
文件偏號: 4T43NM84