ハードウェア: PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers

問題: 653xデジタルI/Oデバイスのグループ番号の指定はどのようにすべきなのでしょうか

解決策: 653x User manualに記載があるとおり、653xデバイスではグループ1とグループ2の二つのグループへの割り当てが可能です。
これはLabVIEWのアプリケーションとしてグループ1と2しか割り当てることができないことを意味しているわけではなく、LabVIEWではグループ番号は0から15までの番号を割り当てることが可能です。
作成しているLabVIEWのアプリケーションで二つのグループを使用している場合、グループ番号を(0,1)、(1,2)、(4,9)のように割り当てることが可能です。

例えば、ポート0とポート1を入力として、ポート2とポート3を出力として使用することを想定した場合、Digital Group Config VIを使用してポート0とポート1をグループ3として、ポート2とポート3をグループ10として割り当てることが可能です。
反対にポート0とポート1をグループ10として、ポート2とポート3をグループ4として割り当てることも可能です。

基本的にはDIO Config VIのグループ入力とハードウェア的なグループとは関係はありません。
また、使用するグループが一つのみの場合はこの入力は必要ありません。
両方のハンドシェークグループが使用される場合のみDIO Config VIのグループ入力へ割り当てる番号を指定する必要があります。

関連リンク:

653x user Manual for Traditional NI-DAQ

KnowledgeBase 1YMA33PH: NI-653xデバイスのポートの構成はどのように行えばよいのでしょうか



添付:





報告日時: 10/07/2002
最終更新日: 03/19/2009
ドキュメントID: 2Q6K112O