Can I Disable the Filter on the [c]FP-AI-110, [c]FP-AI-111, or [c]FP-SG-140? Hardware: FieldPoint>>Analog I/O Modules>>FP-AI-110
Problem: The [c]FP-AI-110, [c]FP-AI-111, and [c]FP-SG-140 have software-selectable input notch filter settings. The update rate for all channels depends on the filter frequency selected. Is it possible to disable the filter or to obtain a faster update rate than those listed in the manuals? Solution: No, there is no way to disable the filter. The fastest update rate is obtained by setting the filter to the highest frequency setting. For the AI-11x, this is 500 Hz; for the SG-140 this is 240Hz. By default, the filters for all three modules are set to 60 Hz, which is the medium setting. Please see the table below for the exact specifications. Filter Settings for the [c]FP-AI-110, [c]FP-AI-111, and [c]FP-SG-140
The filter in the FieldPoint analog input module functions by measuring the voltage drop of a signal across a highly accurate input resistor. The information is used to reject noise from the incoming signal. Noise can be introduced externally to a signal which can affect the incoming voltage. This is why filters may be desirable - to eliminate any noise in the incoming voltage signal and provide a cleaner measurement. Related Links: Product Manuals: FP-AI-110 and cFP-AI-110 Operating Instructions Product Manuals: FP-AI-111 and cFP-AI-111 Operating Instructions Product Manuals: FP-SG-140 and cFP-SG-140 Operating Instructions KnowledgeBase 3J39RNPH: How Do I Change the Filter Settings of a [c]FP-AI-11x or [c]FP-SG-140? Attachments:
Report Date: 01/09/2003 Last Updated: 09/16/2008 Document ID: 2T8APBP6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||