Archived: 従来型DAQの"AO構成"("AO HW構成")実行時のエラー10012について

This document has been archived and is no longer updated by National Instruments



ハードウェア: PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers, PXI/CompactPCI>>Controllers

問題: 従来型DAQの"AO構成"("AO HW構成")実行時にエラー10012が発生するのはどうしてですか?
従来型DAQの"AO構成"("AO HW構成")の"範囲設定"クラスタで、"基準ソース(変更なし:0)"を"no change" にし、"上限"、"下限"を、-10、10や0、10などにした場合はエラーは発生しませんが、それ以外の値を設定するとエラー10012が発生します。どうしてですか?

解決策: LabVIEWのヘルプに、”上限と下限はデバイスで使用可能な範囲に指定する必要があります。”となっています。ここでいう範囲は、-10~10や0~10Vといったデバイスで設定できるレンジであり、例えば、-10~10と0~10Vを設定できるデバイスでは、-10~10と0~10Vのいずれかしか設定できません。-10~10Vの範囲内だからといって-2~5Vといった設定をすることはできません。エラー10012が発生しない場合は、上限と下限の設定値がそのデバイスで設定できるもので、エラーが発生する場合は、設定値がそのデバイスでは設定できない値ということになります。
デバイスに希望の設定値が無い場合は、希望の電圧の外部リファレンスを使用します。外部リファレンス電圧を使用する場合は、外部リファレンス電圧をEXTREFピンに接続して、"基準ソース(変更なし:0)"を"external"、 上限値に外部リファレンス(ExtRef) の電圧を設定してください。

外部リファレンス電圧を使用する場合は、DAQ(データ集録)ボードのユーザーマニュアルのアナログ出力リファレンス(analog output reference)の項目に詳細がありますので、そちらも参照してください。

関連リンク: Product Manuals: DAQ E Series User Manual

添付:





報告日時: 08/16/2002
最終更新日: 03/19/2009
ドキュメントID: 2OFG645A