Error -34107 when running a LabVIEW Executable that access a FieldPoint Network Module Primary Software: LabVIEW Modules>>Real-Time ModulePrimary Software Version: 7.1 Primary Software Fixed Version: N/A Secondary Software: N/A
Problem: I have an executable, built in LabVIEW 7.x, that accesses a FieldPoint Network module, but I am receiving the following error: Error -34107 occurred at an unidentified location Possible reason(s): FieldPoint: Unable to load the FieldPoint server .dll. Possible cause: The .dll does not support the required interface. Solution: To clear this error install the FieldPoint Drivers (4.x or later) with Support for LabVIEW on the machine running the executable. Related Links: KnowledgeBase 19HBJ2LK: Creating a FieldPoint Executable in LabVIEW or LabWindows/CVI Attachments:
Report Date: 03/14/2008 Last Updated: 03/14/2008 Document ID: 4JD924DO |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||