Error -200077 (0xFFFCF273) During Thermocouple Measurements with SCB-68 or SCXI

Primary Software: Utility Software>>Measurement & Automation Explorer
Primary Software Version: 3.1
Primary Software Fixed Version: N/A
Secondary Software: N/A
Hardware: Counter/Timers (TIO)>>Connectivity>>SCB-68, SCXI>>Modules>>SCXI-1102

Problem:
Why is using a DAQ device with the SCB-68 or SCXI-1102 for Thermocouple Measurements with Built-In CJC Compensation Yield -200077 Error?

Solution:
SCXI-1102
  1. Launch Measurement and Automation Explorer and navigate to the SCXI-1102 module

  2. Right-click the SCXI-1102, and select Properties

  3. Select the Accessory Tab

  4. Ensure that the Accessory in the drop down menu has CJC capabilities (such as the SCXI-1303)

SCB-68
  1. Launch Measurement and Automation Explorer and navigate to the DAQ device that is attached to the SCB 68

  2. Right-click on the DAQ device and select Properties

  3. Select the Accessory Tab

  4. Ensure that under Accessory drop down box the SCB 68 is selected, then left-click the Configure button

  5. Under the CJC Configuration tab, ensure that the " Temperature Reference Enabled " checkbox is checked.

  6. Ensure that temperature reference sensor is enabled on the SCB 68. This can be found on page 4-3 of SCB 68 User Manual (Linked below)



Related Links:
SCB 68 User Manual
KnowledgeBase 3UKG06X1: Conflicting Range Values in Thermocouple Task Cause Error -200077