Academic Company Events NI Developer Zone Support Solutions Products & Services Contact NI MyNI
This Document is not yet Rated  Rate this Document

Error -200077 (0xFFFCF273) During Thermocouple Measurements with SCB-68 or SCXI

Primary Software: Utility Software>>Measurement & Automation Explorer
Primary Software Version: 3.1
Primary Software Fixed Version: N/A
Secondary Software: N/A
Hardware: Counter/Timers (TIO)>>Connectivity>>SCB-68, SCXI>>Modules>>SCXI-1102

Problem:
Why is using a DAQ device with the SCB-68 or SCXI-1102 for Thermocouple Measurements with Built-In CJC Compensation Yield -200077 Error?

Solution:
SCXI-1102
  1. Launch Measurement & Automation Explorer and navigate to the SCXI-1102 module
  2. Right-click SCXI-1102 and select Properties
  3. Select the Accessory tab
  4. Ensure that the Accessory in the drop down menu has CJC capabilities (such as the SCXI-1303)
SCB-68
  1. Launch Measurement & Automation Explorer and navigate to the DAQ device that is attached to the SCB-68
  2. Right-click on the DAQ device and select Properties
  3. Select the Accessory tab
  4. Ensure that under Accessory drop down box the SCB-68 is selected, then left-click the Configure button
  5. Under the CJC Configuration tab, ensure that the Temperature Reference Enabled checkbox is checked.
  6. Ensure that temperature reference sensor is enabled on the SCB-68. This can be found on page 4-3 of SCB 68 User Manual (Linked below)


Related Links:
SCB 68 User Manual
KnowledgeBase 3UKG06X1: Conflicting Range Values in Thermocouple Task Cause Error -200077

Attachments:





Report Date: 07/11/2005
Last Updated: 05/08/2009
Document ID: 3NAFKU9N

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5
Please Contact NI for all product and support inquiries.submit