How Do I Resolve VISA Error -1073807202 (0xBFFF009E) on FieldPoint RT Controllers?

Primary Software: LabVIEW Modules>>LabVIEW Real-Time Module
Primary Software Version: 7.1
Primary Software Fixed Version: N/A
Secondary Software: N/A
Hardware: FieldPoint

Problem:
How Do I Resolve VISA Error -1073807202 (0xBFFF009E) on FieldPoint RT Controllers?



Solution:
Make sure that NI-Serial RT is installed on the [c]FP controller. To install software on your FieldPoint controller, follow these steps:
  1. Open Measurement & Automation Explorer (MAX).
  2. Navigate to Remote Systems » Name of your FieldPoint Bank.
  3. Right-click on Software.
  4. Select Add/Remove Software.
  5. The following window will appear and allow you to install software on your FieldPoint RT controller.  Click once on the gray arrow and select Install the feature.
  6. Click Next » Next » Finish.  The controller will reboot automatically with the new software installed.




Related Links:
KnowledgeBase 2PB8A8DS: How Do I Resolve VISA Error -1073807202 (0xBFFF009E)?

Attachments:





Report Date: 03/18/2005
Last Updated: 07/31/2009
Document ID: 3JHAHIPH

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5