Academic Company Events NI Developer Zone Support Solutions Products & Services Contact NI MyNI
This Document is not yet Rated  Rate this Document

Measuring the 100Ω Resistance on [c]FieldPoint Current Input Modules

Hardware: FieldPoint>>Analog I/O Modules>>FP-AI-100, FieldPoint>>Analog I/O Modules>>FP-AI-110, Compact FieldPoint>>Analog I/O Modules>>cFP-AI-100, Compact FieldPoint>>Analog I/O Modules>>cFP-AI-110

Problem:
When I try to measure the resistor between the current input and ground pins of my [c]FP-AI-1x0, I see infinite resistance. Why do I not see 100Ω like the documentation indicates?

Solution:
The power to the FieldPoint hardware must be on in order to correctly measure the 100Ω resistor between the current input pin and the ground (COM) pin for an analog input current channel on a [c]FP-AI-1x0 module. When the hardware is powered off, the resistance between these pins is infinite. Please refer to Figures 6 and 7 in the operating instructions (see related links below) of these FieldPoint modules for proper current input connection diagrams that also illustrate the 100Ω resistor in question.

Related Links:
Product Manuals: [c]FP-AI-100 Operating Instructions
Product Manuals: [c]FP-AI-110 Operating Instructions

Attachments:





Report Date: 04/07/2006
Last Updated: 05/15/2006
Document ID: 3W66QJF3

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5
Please Contact NI for all product and support inquiries.submit