NI-FBUS Alert Handling Problems Primary Software: Driver Software>>NI-FBUSPrimary Software Version: 2.3.5 Primary Software Fixed Version: N/A Secondary Software: N/A
Problem: If the confirmation of an alert fails, then NI-FBUS does not re-try in all conditions, and the alert can be left there without confimation. Also, if the device re-uses an event number in an alert, then the NI-FBUS might regard the new alert as a re-transmission of the old alert. Therefore, the event number is not the only parameter to check to see if an alert is new. The alert state or a timestamp should be used to identify the alert (a confirmed alert should not have re-transmission). How can I fix these problems? Solution: These problems are fixed in NI-FBUS version 2.3 and later. Please visit the Related Link below to download the latest version of the Foundation Fieldbus drivers. Related Links: Drivers and Updates: Current Software Versions by Product Attachments:
Report Date: 01/29/1998 Last Updated: 12/02/2004 Document ID: 15SAO7EG |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||