Configuring the SCC-CTR01 in MAX

Hardware: SCC>>Modules>>SCC-CTR01

Problem: I am trying to add the SCC-CTR01 to my SC-2345 carrier in Measurement and Automation Explorer (MAX) but it does not show up in the drop down list. How can I configure and use this module?

Solution: The inputs of this module can be configured by creating a counter task for the corresponding counter inputs of the DAQ device. Reference this counter task when performing counter measurements. The SCC-CTR01 does not need to be configured in the SCC-2345 carrier in MAX to function properly.