I Am Not Getting Any Frequency Readings When Using the SCC-FV01.

Hardware: SCC>>Modules>>SCC-FV01

Problem: I am trying to use the SCC-FV01 to measure a frequency signal that goes anywhere from 0 to 10 Volts. When I test it in MAX, it doesn't seem to be working.

Solution: The FV01 has a zero-crossing detector in order to measure frequency inputs, so your input signal has to go from positive to negative values and back for this module to work properly.