Problem:
I created digital line and port virtual channels for the NI PCI-6025E (or AT-MIO-16DE-10) in Measurement & Automation Explorer (MAX). My virtual channels for reading or writing to a port work fine in the Virtual Channel Test Panel. My virtual channels for reading or writing to a line in Ports PA, PB, or PC return Error -10007 occurred at Digital Group Config in the Virtual Channel Test Panel (lines in Port DIO do not return an error). Can I use Read from Line or Write to Line Virtual Channels whose lines are in Ports PA, PB, or PC in LabVIEW?

Solution:
Yes, you can use both Read from Line and Write to Line Virtual Channels whose lines are in Ports PA, PB, or PC in LabVIEW. To use these Virtual Channels, you must use DIO Port Config.vi not Digital Group Config.vi. Using Digital Group Config.vi returns Error -10007 just like the Virtual Channel Test Panel in MAX. This error is caused because the digital lines from the 8255 PPI (programmable peripheral interface), Ports PA, PB, and PC, cannot be individually configured (please refer to KnowledgeBase 041A1KNI linked below for more information).

Note: Read from Digital Line.vi and Write to Digital Line.vi do not return errors because they use DIO Port Config.vi.

Related Links:
KnowledgeBase 041A1KNI: On Which Boards Can DIO (Digital Input/Output) Lines Be Individually Configured?
KnowledgeBase 2L8E72P6: What Is the 82C55A and Which NI Products Use This Chip?
KnowledgeBase 2GIICLDJ: Error -10007 When Using the Digital Line Functions With E Series Devices

Attachments:





Report Date: 07/09/2002
Last Updated: 06/10/2009
Document ID: 2N89NPT0

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5
Please Contact NI for all product and support inquiries.submit