Do I need to Install Support for Shared Variable on TPC-2012?

Primary Software: LabVIEW Modules>>Touch Panel Module
Primary Software Version: 1.0
Primary Software Fixed Version: N/A
Secondary Software: LabVIEW Modules>>Touch Panel Module
Hardware: Industrial Communications>>HMI and Industrial PC>>TPC-2006

Problem:
I have an application using shared variables developed to run on TPC-2012. However, the install option on the project explorer is only available for ARM-based processor. How do I install support for shared variable on TPC-2012?

Solution:
The TPC-2012 is an x86-based processor and comes with preinstalled support for shared variable. Hence, you do not need to install support for shared variable on TPC-2012.

If you install support for shared variable using the (ARM) option, then each time you power on or reboot the TPC-2012, it will always prompt to keep or replace the existing installation files. These files include the nitaglvpda.dll, lkdynamic.dll, lksec.dll and lksock.dll.

To remove this installation,

  1. Browse to HardDisk\wince\Config\ on the TPC 2012
  2. Delete the National Instruments LabVIEW 8.2 Shared Variable Support.CAB
  3. Reboot the TPC-2012



Related Links: