Why Are My Temperature Values Incorrect When Using Optomux Commands to Read My FP-TC-120?Primary Software: Driver Software>>NI-FieldPointPrimary Software Version: 4.1 Primary Software Fixed Version: N/A Secondary Software: N/A Hardware: FieldPoint>>Analog I/O Modules>>FP-TC-120
Problem: When I monitor the temperature readings in Fieldpoint Explorer or Measurement and Automation Explorer (MAX), the temperature values seem fine. However, when a program using optomux commands accesses the module, the values returned are wrong. Why? Solution: The correct command to use when reading a FP-TC-120 scaled temperature value is !G. A common mistake is to use the L command instead which will yield incorrect results. This is discussed on page 38 of the programmer reference manual linked below. Related Links: FP-1000/1001 Programmer Reference Manual FP-TC-120 and cFP-TC-120 Operating Instructions Attachments:
Report Date: 09/12/2001 Last Updated: 04/05/2005 Document ID: 2DBCC46W |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||