What Are the Set Attributes Setting Codes for the FP-AI-112?

Hardware: FieldPoint>>Analog I/O Modules>>FP-AI-112

Problem: I would like to programmatically set the range of a FP-AI-112. Since I am using a FP-1000/1001, the Set Attributes Optomux command (pg 5-9 FP-1000/1001 Programmer Manual) is the way to do this; however, the latest version of this manual is March 1999 and the FP-AI-112 is not listed. I need the range/settings table like the one provided on page 5-12 of the FP-1000/1001 Programmer Manual.

Solution: The range/settings table for using the Set Attributes Optomux command with the FP-AI-112 is provided below.
VoltageCode
+/- 10V03
0-10V04
+/- 5V05
0-5V06
+/- 1V07
0-1V08
+/- 300 mV09
+/- 60 mV0A


Related Links: FP-1000/1001 Programmer Manual