OPC Interface for LabVIEW Datalogging and Supervisory Control Module Not in the Server ExplorerPrimary Software: LabVIEW Modules>>DSC ModulePrimary Software Version: N/A Primary Software Fixed Version: N/A Secondary Software: N/A
Problem: I have installed the LabVIEW Datalogging and Supervisory Control (DSC) Module, but I don't see its OPC Interface in the Server Explorer. Solution: The OPCLabVIEW server is not visibile because it is not registered, or LabVIEW DSC 7.1 or earlier are not being used. The OPCLabVIEW server was replaced by the Shared Variable Engine for sharing data in LabVIEW DSC 8.0 and above. The LabVIEW DSC Module 7.1 installs the OPC interface automatically. You don't have to make any special selection during installation process. However, the OPC interface is not registered by the installer. It is registered by the DSC Module upon first execution. You need to run the module at least once to get the 'OPCLabVIEW' available in the Server Explorer. If you have done so, but the interface is still not available, try to run the following VI: Note: The LabVIEW DSC Module 8.x is significantly different than the DSC Module 7.x. Refer to the Release Notes below to learn about the changes. Related Links: LabVIEW Datalogging and Supervisory Control Module 8.0 Release and Upgrade Notes COM: Component Object Model Technologies Attachments:
Report Date: 01/05/2001 Last Updated: 07/26/2007 Document ID: 2548C4J6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||