Academic Company Events NI Developer Zone Support Solutions Products & Services Contact NI MyNI
1 ratings:
 5 out of 5     Rate this Document

cFP-DI-304 Update Utility

Hardware: Compact FieldPoint>>Discrete I/O Modules>>cFP-DI-304

Problem:
Why does my cFP-DI-304 return incorrect data when performing a single FieldPoint Read?

Solution:
This is a known issue that affects revision C and earlier Compact FieldPoint cFP-DI-304 modules. If a cFP-DI-304 is returning data either to an application running embedded on a Real-Time controller or from a cFP-180x over a serial connection, a single read may not return the current states of the module channels. You likely will not notice the problem if you are performing repeated reads (i.e. inside a loop).

If a host PC is communicating with the cFP-DI-304 over Ethernet, the problem may appear as a significant delay before data is correct. In other words, after the module channels change state, a single read over Ethernet will return the current states if there is sufficient wait time before performing the query.

National Instruments has developed a utility that can upgrade the cFP-DI-304 firmware and correct this problem. You need a Real-Time controller and certain software to run the utility yourself. Use the table below to determine if your hardware / software will support the utility and to download the appropriate version. Instructions on using the utility are included with the download. If you need assistance running the utility, please call 1-877-493-2406 and ask to speak with an Applications Engineer.

If you need to return your cFP-DI-304 module for upgrade, please call National Instrumentes at 1-877-493-2406 to obtain a service request number and to arrange shipping. National Instruments will repair the affected module(s) at no cost to you.

Please accept our apology for the inconvenience. National Instruments is committed to your total satisfaction and to maintaining your confidence in our products.


Controller Model
[c]FP-20xx
cFP-21xx
cFP-180x

  LabVIEW  7.0  
 
  Return to NI for Upgrade  
  Return to NI for Upgrade  
  Return to NI for Upgrade  

  LabVIEW  7.1  
 
  Return to NI for Upgrade  
  Update Utility  
  Return to NI for Upgrade  

  LabVIEW  8.x  
 
  Update Utility  
  Update Utility  
  Return to NI for Upgrade  


Related Links:

Attachments:


cFP-DI-304 Update for LV 71.zip cFP-DI-304 Update for LV 8x.zip


Report Date: 02/27/2007
Last Updated: 03/29/2007
Document ID: 46QDP9Q8

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5
Please Contact NI for all product and support inquiries.submit