"Unable to Locate Component Error" with NI OPC Server installed with LabVIEW 8.5.1 DSC Module Primary Software: LabVIEW Modules>>DSC ModulePrimary Software Version: 8.5.1 Primary Software Fixed Version: N/A Secondary Software: LabVIEW Development Systems>>Full Development System
Problem: When I try to add a new channel to NI OPC Servers, I get the following set of errors. Why does this happen? Solution: This is a known error when you create a new channel in NI OPC Servers after installing LabVIEW 8.5.1. Once the errors are cleared a new channel can be created normally. To remove the error, go to <National Instruments>\Shared\NI OPC Servers\ and rename the file "customlicensing.dll" to "customlicensing.dll.bak". Close and reopen NI OPC Servers.Related Links: Attachments:
Report Date: 04/22/2008 Last Updated: 04/23/2008 Document ID: 4KLM1J3Y |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||