Academic Company Events NI Developer Zone Support Solutions Products & Services Contact NI MyNI
This Document is not yet Rated  Rate this Document

Error 1055 When Running a LabVIEW DSC Executable

Primary Software: LabVIEW Modules>>DSC Module
Primary Software Version: 8.0
Primary Software Fixed Version: N/A
Secondary Software: LabVIEW Run-Time Engine

Problem:
I created an executable that includes LabVIEW Datalogging and Supervisory Control functions.  The LabVIEW DSC Run-Time System is installed.  Why do I get Error 1055 when running the application? 

Solution:
When used in an executable, certain tasks require the enhanced DSC Module Run-Time Engine.  This applies to functions which programmatically change a library, such as the Save to Library VI.

You must choose to include the enhanced DSC Run-Time Engine before building the application.  This option is under the Advanced category of the application properties. When creating the build specification, check Enable Enhanced DSC Run-Time support as shown below.



Build and run the application again, and the error should be gone.

Related Links:
LabVIEW 8.6 Help: Advanced Page (Application Properties Dialog Box)
KnowledgeBase 2PQEO6Q2: Building a LabVIEW DSC Executable Without the DSC Run-Time System
Products and Services: LabVIEW Datalogging and Supervisory Control Module, Run-Time System

Attachments:





Report Date: 04/18/2009
Last Updated: 01/11/2010
Document ID: 4WHEQ103

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5
Please Contact NI for all product and support inquiries.submit