Error 10003 occurs when performing SCXI_SCAN_Config or SCXI_SCAN_Setup. Primary Software: LabVIEW Development Systems>>Professional Development SystemPrimary Software Version: 8.0 Primary Software Fixed Version: N/A Secondary Software: Driver Software>>NI-DAQmx Hardware: SCXI>>Chassis>>SCXI-1000
Problem: Why do I get error -10003 when I call SCXI_SCAN_Config or SCXI_SCAN_Setup with a call library function node? Solution: The values passed into these functions, particularly the DAQboard and modeFlag parameters, should be passed as "Value", not "Pointer to Value." Related Links: KnowledgeBase [0ZUEBQN9]: Error 10003 Returned by MAX When a Channel is Named SCXI1, SCXI2, etc. Attachments:
Report Date: 09/11/2006 Last Updated: 09/29/2006 Document ID: 41AE252F |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||