Multiplexer Expansion with NI Switch Executive Primary Software: Switch ExecutivePrimary Software Version: 2.1 Primary Software Fixed Version: N/A Secondary Software: N/A
Problem: I need to create a multiplexer switching configuration that has more channels than any single multiplexer module available from National Instruments. Can I can achieve this goal using multiple switch modules and NI Switch Executive? Solution: Yes, the COM terminals of two or more multiplexer modules can be connected to increase the channel count of a multiplexer configuration. However, it is very important that only one of the input channels on any of the modules is connected at any given time. Otherwise, the configuration is not truly a multiplexer and there is a risk of shorting input channels together and damaging hardware. In order to guarantee that only a single channel on any of the modules is connected to the shared COM terminal, there must be exclusions defined in software. NI Switch Executive allows for software defined exclusions such as this, and makes this particular configuration, along with a variety of other custom configurations, simple to implement. Below are the steps needed to accomplish this:
Related Links: Product Page: NI Switch Executive Attachments:
Report Date: 09/25/2006 Last Updated: 10/27/2006 Document ID: 41ODDALA |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||