当我在Class I, Div 2环境下使用Compact Fieldpoint,是否需要安装本安防爆栅?

硬件: Compact FieldPoint>>Controllers>>cFP-2000

问题: 当我在Class I, Div 2环境下使用Compact Fieldpoint,是否需要安装本安防爆栅?

解答: 当在Class I, Div 2环境下使用Compact Fieldpoint,不需要安装本安防爆栅。本安防爆栅是在Div 1级别的危险区域下采用的保护措施。"cFP 是不易燃的"(功率受到限制),因此可以安全使用在Class I, Div 2环境下。

关于Class I, Div2环境定义请参考下面链接Electrical Equipment and Safety Standards。

相关链接: Product Certification: Compact FieldPoint
Product Certification: FieldPoint
Electrical Equipment and Safety Standards