Why Do I Get an Error When Writing to a Lookout Object in Server Explorer?

Primary Software: Lookout
Primary Software Version: 5.0
Primary Software Fixed Version: N/A
Secondary Software:

Problem: I have a switch object in my Lookout process, and I can successfully read it in Server Explorer. But, when I try to write to it, I receive the following message: "The Items AccessRights does not allow the operation".

Solution: If you specify an object without specifying a data member, you are implying the implicit data member. Because the implicit data members are read-only, you cannot write to them or make a remote connection to them. For example, to specify the position of a Switch as a read/write value, you would use the Switch's value data member.

Related Links: KnowledgeBase 1ZRA623V: Alarm in Lookout: Remote position source not writable