What Grounding Mode Should I Select When Using the SC-2345 Carrier for SCC Modules?Hardware: SCC>>Carriers>>SC-2345
Problem: I am going to use an SC-2345 carrier with my NI data acquisition device. What measurement mode should I select: differential (DIFF), referenced single ended (RSE), or non-referenced single ended (NRSE)? Solution: The DAQ device should be set to NRSE mode when using the SC-2345. Version 2.1 and higher of Measurement & Automation Explorer (MAX) will automatically set the card to NRSE mode when an SC-2345 is selected as the signal accessory. Related Links: Product Manuals: SCC-AI Series User Manual Attachments: