How Much Control Do I Have in DASYLab Over the Pulse Train Functionality of My National Instruments Counter?Primary Software: Other NI Software>>DASYLabPrimary Software Version: 6.00.03 Primary Software Fixed Version: N/A Secondary Software: N/A
Problem: I would like to know the limits of DASYLab's Frequency Output module with my National Instuments DAQ board. Solution: Q: Can DASYLab generate a user configurable pulse train on a National Instruments DAQ board? A: Yes Q: What is the maximum pulse train frequency for which I can configure a counter in DASYLab using the Frequency Output module?
Q: Can I manually select which timebase my counter uses for the pulse train generation? A: No, DASYLab will automatically select the appropriate internal timebase based on which frequency you have selected. Q: Can I manually change the output mode of my counter from the default Toggled mode to Pulsed mode in DASYLab? A: No, DASYLab only supports using a counter in the default Toggled output mode. If you need to use the Pulsed output mode functionality of your counter consider using a different programming environment that allow full control of our DAQ driver such as LabVIEW or Visual C++. Related Links: What Is the Maximum Output Frequency I Can Obtain with the PCI-6601 or the PCI-6602? Attachments:
Report Date: 08/28/2003 Last Updated: 12/07/2004 Document ID: 30RE7N2G |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||