I Cannot Detect Slot 8 in my Compact FieldPoint BackplanePrimary Software: Driver Software>>NI-FieldPointPrimary Software Version: N/A Primary Software Fixed Version: N/A Secondary Software: N/A Hardware: Compact FieldPoint>>Controllers>>cFP-2110, Compact FieldPoint>>Controllers>>cFP-2120, Compact FieldPoint>>Controllers>>cFP-2100
Problem: I have a 21xx or 20xx series controller, and recently upgraded to FieldPoint 6.0.2. Since upgrading, I cannot detect any module in slot 8. How can I correct this problem? Solution: A small bug was introduced in FieldPoint 6.0.2 that prevents a 20xx or 21xx series controller from detecting modules in slot 8. In order to correct the problem, you must install FieldPoint 6.0.3 or higher.
Related Links: NI-FieldPoint 6.0.3 Attachments:
Report Date: 08/27/2008 Last Updated: 10/27/2008 Document ID: 4OQBDHHN |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||