Are Digital Lines Reserved on VXI-MIO DAQ Devices When Using VXI-SC?

Hardware: VXI/VME/MXI>>VXI Data Acquisition and Instrument Modules, VXI/VME/MXI>>VXI Signal Conditioning

Problem: Are digital lines reserved on VXI-MIO DAQ devices when using VXI-SC?

Solution: When using plugin DAQ devices with SCXI, certain digital lines will be reserved. For example, E-series plugin DAQ devices have digital lines 0,1, and 2 reserved for output and line 4 reserved for input.

The same applies to VXI-MIO devices that are using VXI-SC. For example, if you are using a VXI-MIO-64E-1 with a VXI-SC-1000 chassis and VXI-SC-1102 module, digital lines 0,1,2, and 4 on the VXI-MIO-64E-1 will be reserved.