Academic Company Events NI Developer Zone Support Solutions Products & Services Contact NI MyNI
This Document is not yet Rated  Rate this Document

What Happens When Communication Fails To My NI 9144 Expansion Chassis?

Hardware: CompactRIO>>Chassis (Backplanes)

Problem:
What happens to my NI 9144 and the modules it contains when communication to the master device fails, or the master loses power?

Solution:
The NI 9144 will enter into a safety state if the Sync Manager Watchdog times out.  The default timeout is set to 10 scan periods.  All input and and output values will become 0 (zero) in this case.  As soon as the connection is re-established the outputs would need to be updated to have a different value from zero.

For an example on how to recover from this state once connection to the master has been re-established, see the attached project.

Related Links:
Can I Use the NI 9144 EtherCAT Expansion Chassis in FPGA Mode?
Developer Zone Tutorial: Introduction to EtherCAT

Attachments:
Clear_Watchdog_SE.zip




Report Date: 06/06/2009
Last Updated: 07/10/2009
Document ID: 4Y5EKS6C

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5
Please Contact NI for all product and support inquiries.submit