MAX Error 56 When Communicating With a LabVIEW Real-Time Controller Primary Software: LabVIEW Modules>>Real-Time ModulePrimary Software Version: 8.5 Primary Software Fixed Version: N/A Secondary Software: N/A Hardware: CompactRIO>>Controllers, Compact FieldPoint>>Controllers, Compact FieldPoint>>Controllers, FieldPoint>>Controllers/Network Modules, Image Acquisition (IMAQ)>>Compact Vision System, PXI/CompactPCI>>Controllers
Problem: I receive Error 56 in Measurement and Automation Explorer (MAX) when I try communicating with my Real-Time controller. My controller is connected with a cross-over cable. The error occurs in one or more of the following situations:
Solution: This error is typically caused by specifying a gateway IP address for the controller when one does not exist. Change the gateway IP address on the real-time controller to 0.0.0.0 or leave it blank, as seen below. ![]() Click on the Apply button followed by the Reboot button to put the changes into effect. The gateway is used to route packets to outside networks. A typical Windows machine does not function as a gateway and causes the real-time controller to time out when it does not respond to the Real-Time controller's requests for a gateway. Related Links: KnowledgeBase 2FF6N4KN: Choosing an IP Address for Your Real-Time Engine KnowledgeBase 2RHCS8M5: How Do I Change the IP Address of a RT Series Controller (FieldPoint, cRIO, etc) that is not on the Local Subnet? Attachments:
Report Date: 06/30/2006 Last Updated: 02/25/2008 Document ID: 3YTEBIJ8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||