Baud Rate Settings When Calibrating an FP-TC-120 with Calibration Executive

Primary Software: Calibration Executive
Primary Software Version: 3.0
Primary Software Fixed Version: N/A
Secondary Software: N/A
Hardware: FieldPoint>>Analog I/O Modules>>FP-TC-120, FieldPoint>>Controllers/Network Modules>>FP-1001, FieldPoint>>Controllers/Network Modules>>FP-1000

Problem: What baud rate should I set on my FieldPoint controller in order to calibrate my FP-TC-120?

Solution: In order to successfully calibrate the FP-TC-120, you must set your baud rate to 115200. This is accomplished by setting all of the dip switches on the controller to the up position. Also, ensure that the baud rate setting in Calibration Executive matches the same 115200 rate. This will allow you to correctly calibrate the module.

Related Links:
KnowledgeBase 3E6B0660: Calibrating FieldPoint Modules Using a FieldPoint 2000 with Calibration Executive

Required Calibration Equipment

Attachments:





Report Date: 10/22/2004
Last Updated: 10/22/2004
Document ID: 3ELCONHS

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5