Error -201247 When Adding WLS or ENET C-Series Module in Measurement & Automation Explorer
Hardware: CompactDAQ>>Digital Input Modules>>NI 9421
Problem: I have an NI WLS-9163 or ENET-9163 with a C-Series module plugged in. I can find the device in Measurement & Automation Explorer but when I try to add the device just found, I receive the following error message:
Error -201247 occurred at Add Networked DAQ Devices...
Possible reason(s):
Measurements: Device cannot be created in MAX because a driver could not be found for the device. You may need to upgrade NI-DAQmx.
Solution: This error will occur if you are trying to use an unsupported C-series module with the NI WLS/ENET-9163. As stated in the overview tab for the NI WLS/ENET-9163 product page, the only C-series modules supported are as follows:
NI-DAQmx 8.8 supports these five modules:
- NI 9211 (4-channel, 14 S/s, 24-bit, ±80 mV thermocouple input)
- NI 9215 (4-channel, 100 kS/s/ch, 16-bit, ±10 V analog input)
- NI 9219 (4-channel, 100 S/s/ch, 24-bit, ±60 V, ±25 mA universal input)
- NI 9234 (4-channel, 51.2 kS/s/ch, 24-bit, ±5 V IEPE input)
- NI 9237 (4-channel, 50 kS/s/ch, 24-bit, ±25 mV/V bridge and strain input)
NI-DAQmx 8.9 added support for the following three modules:
- NI 9421 (8-Channel 24 V Logic, 100 µs, Sinking Digital Input Module)
- NI 9472 (8-Channel 24 V Logic, 100 µs, Sourcing Digital Output Module)
- NI 9481 (4-Channel Relay [30 VDC (2 A), 60 VDC (1 A), 250 VAC (2 A)])
NI-DAQmx 9.0 added support for the following three modules:
- NI 9205 (32-Ch ±200 mV to ±10 V, 16-Bit, 250 kS/s Analog Input Module)
- NI 9206 (16-Ch ±200 mV to ±10 V, 16-bit, Analog Input for Fuel Cells)
- NI 9213 (16-Channel Thermocouple Input Module)
Related Links: NI WLS-9163NI ENET-9163NI-DAQ 8.8 ReadmeNI-DAQ 8.9 ReadmeNI WLS/ENET-9163 User Guide and SpecificationsNI-DAQmx for the WLS/ENET-9163 Getting Started Guide