Academic Company Events NI Developer Zone Support Solutions Products & Services Contact NI MyNI
This Document is not yet Rated  Rate this Document

Errors When the Alert_Key Parameter Is Set to Zero (Default)

Primary Software: Driver Software>>NI-FBUS
Primary Software Version: 2.3.5
Primary Software Fixed Version: N/A
Secondary Software: N/A

Problem: Why do I receive errors when the Alert_Key parameter is set to zero (default) and what can I do to fix this?

Solution: When creating a new block in the Network Configurator, the Alert_Key parameter always defaults to 0. According to the Fieldbus specification, this is an illegal value and errors will be generated accordingly. In order to prevent these errors from appearing, it is necessary to set the Alert_Key parameter to a number greater than zero. Valid settings for the Alert_Key parameter range from 1 to 255. Typically this value is used in the host for sorting alarms.

Related Links:

Attachments:





Report Date: 11/15/2000
Last Updated: 12/09/2004
Document ID: 23EACO6W

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5
Please Contact NI for all product and support inquiries.submit