Why Do I Get Error -2147023838 When Configuring My OPC Client I/O Server?

Primary Software: LabVIEW Modules>>DSC Module
Primary Software Version: 1.0
Primary Software Fixed Version: N/A
Secondary Software: N/A

Problem:
I am using LabVIEW Datalogging and Supervisory Control (DSC) Module to create an OPC Client I/O Server.  As soon as the OPC Client configuration window appears I receive a Browse OPC Error window stating that error -2147023838 occurred at getopcserverlist.vi.  Why can't I configure my OPC Client?



Solution:
The error shown in the image below will appear if the OpcEnum service is not able to start.  To ensure that the service is configured properly navigate to Start » Control Panel » Administrative Tools » Services and locate OpcEnum in the list.  Change the startup type to automatic. 

 



Related Links:
LabVIEW Datalogging and Supervisory Control
KnowledgeBase 3RM8LCSU: Why Do I Get Error -2147024891 When Trying to Connect to My OPC Server?