How Can I Add Language Support For an 8196 Controller With Embedded Software CD 1.3? Primary Software: LabVIEW Modules>>Real-Time ModulePrimary Software Version: 7.1 Primary Software Fixed Version: 8.0 Secondary Software: Driver Software>>NI-DAQmx Hardware: PXI/CompactPCI>>Controllers>>PXI-8196 RT
Problem: Non-ASCII (For example Japanese) channel or task names for DAQmx are not supported without Language Support installed. This is available for other targets, but when I choose Install Software for an 8196, the language support component is not an option. Is this not available? Solution: Navigate to the C:\Program Files\National Instruments\RT Images\Base\1.0 directory and replace the libiconv.cdf file with the attached version. The problem is that a tag is missing from this XML file that informs MAX of which dll's and other files are available for which targets. This will not be a problem in future releases of LabVIEW Real-Time or the Embedded Software CD. Related Links: Attachments:
Report Date: 10/28/2005 Last Updated: 10/31/2005 Document ID: 3QRA97XL |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||