Error-200576 with SCXI-1102 and SCXI-1308 Hardware: SCXI, SCXI>>Modules>>SCXI-1102, SCXI>>Terminal Blocks>>SCXI-1308
Problem: In Measurement and Automation Explorer (MAX), I am getting Error-200576 when I select Built-in as the CJC source in my temperature task. I am using SCXI-1102 module with SCXI-1308 as the terminal block. Why am I receiving this error? Solution: This error is expected behavior as the SCXI-1308 terminal block does not have a built in CJC sensor. Also, the SCXI-1308 is a current input module which is not appropriate for temperature measurement using a thermocouple. Related Links: Manual: SCXI Terminal Block Attachments:
Report Date: 02/05/2007 Last Updated: 02/07/2007 Document ID: 464AK7BH |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||