What Is the Leakage Current Value for the cFP-DO-401?

Hardware: Compact FieldPoint>>Discrete I/O Modules>>cFP-DO-401

Problem:
I am using the cFP-DO-401 and I would like to know what the exact value of the leakage current would be in the OFF state for this device.

Solution:
Due to the absence of protection circuitry on the cFP-DO-401, all of the output leakage will happen through the MOSFET.
When the cFP-DO-401 is in the OFF state, the output transistors between V and Vout are turned off, allowing only a small leakage current to flow. Although the leakage current for this device should be almost zero, the datasheet for the output MOSFET has Zero_Gate_Voltage_Drain_Current at 10uA Max.