 1.5 out of 5     Rate this Document

How Can I Fix Error 32804 at FP Read VI?

Hardware: FieldPoint>>Controllers/Network Modules

Problem:
I create a LabVIEW Project in LabVIEW 8.0 or higher. Then I add a remote target to my project – Ethernet or Real-Time controller. I can see all my modules and all my channels. If I drag a channel from the project to the block diagram of a blank VI, LabVIEW generates FP Read VI code for me. I create an indicator to display the data that I want to read from a given channel. If I delete one of the modules (or the entire remote target) and then add it back to the project, and repeat the steps for reading a channel, I get  Error 32804 at runtime. How can I fix this?

Solution:
Follow the below steps to solve the issue:
  1. Remove the remote target completely from the project
  2. Save the project
  3. Close out of LabVIEW
  4. Save your FieldPoint configuration (.iak) file in MAX
  5. Start LabVIEW
  6. Open your project
  7. Add the remote target
The other option is to create a new project and then add the remote target.

Related Links:
KnowledgeBase 3JA8JPPH: Why Do I Get Error 32812 From Some FieldPoint Modules But Not Others?
KnowledgeBase 39A88TMV: Advantage of Using the FP Write/Read VI
KnowledgeBase 2TL8BHOH: Failed to Download FP Read Basic VI Message When Downloading a VI to a FieldPoint Real-Time Target
KnowledgeBase 2FT7TI90: What Happens if FP Read is Called and the FieldPoint Network Module is Offline?




Attachments:





Report Date: 10/17/2006
Last Updated: 03/28/2008
Document ID: 42GHEALA

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5
Please Contact NI for all product and support inquiries.submit