Do USB Devices Support Continuous Pulse (HW Timed Updates)?

Hardware: Multifunction DAQ (MIO)>>Portable>>USB-6229, Multifunction DAQ (MIO)>>Portable>>USB-6229 OEM, Multifunction DAQ (MIO)>>Portable>>USB-6229 MASS TERM

Problem:
I am trying to generate a continuous pulse train using my USB-6229 or other USB DAQ device and I want to use Continuous Pulse (HW Timed Updates) generation mode.  When I try to do this I get this error: Error -200077 occurred at DAQ Assistant: Requested value is not a supported value for this property

Error - 200077

Is this generation mode supported by my device?



Solution:
Hardware Timed Single Point generation also known as Continuous Pulse (Hardware Timed Updates) is not supported by any of our USB devices. The inherent latency of the USB bus itself does not provide enough determinism to allow this output mode. For a complete listing of the various devices that do and do not support this mode of generation, please refer to KnowledgeBase 4TRGNVH7: Does My DAQ Device Support Hardware-Timing Single Point Sampling Mode?

Related Links:
KnowledgeBase 4TRGNVH7: Does My DAQ Device Support Hardware-Timed Single Point Sampling Mode?
DeveloperZone Tutorial: Choosing the Right Bus for Your Measurement Application
KnowledBase 4GPG2U9S:What Options Do I Have For Hardware-Timed Digital I/O On My M-Series DAQ Device?