Failed to Download FP Read Basic VI Message When Downloading a VI to a FieldPoint Real-Time Target Primary Software: Driver Software>>NI-FieldPointPrimary Software Version: 4.1 Primary Software Fixed Version: N/A Secondary Software: N/A
Problem: Why do I get the message Failed to Download FP Read Basic.vi when I download a VI to my FieldPoint Real-Time Target? Then I get several more message boxes with similar errors. I just upgraded to FieldPoint Explorer 3.0.2 and everything was working before. Also I can still download VI as long as there are no FieldPoint VIs in my program.Solution: You need to download the LabVIEW 6.1.1 firmware. See the attached link for instructions. The error message indicates that the version of FieldPoint VI Manager on the Real-Time target is incorrect. FieldPoint Explorer 3.0.2 introduced faster FieldPoint VIs on the RT target. This change also involved a change in the FieldPoint VI Manager version. Firmware 6.1.0 does not contain the new FieldPoint VI Manager, where as version 6.1.1 does. Also note that the version of LabVIEW Real-Time on the host does not change, it is still 6.1.0. Related Links: KnowledgeBase 2HHJ5N5F. How Do I Change the Version of LabVIEW Real-Time on the [c]FP-20xx Module? Attachments:
Report Date: 01/22/2003 Last Updated: 12/02/2004 Document ID: 2TL8BHOH |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||