Error -200980 when using DAQmx Event with NI USB-9263 Hardware: CompactRIO>>Analog Output Modules>>NI 9263, CompactRIO>>Analog Output Modules>>NI 9263
Problem: I am using the DAQmx "Every N Samples Transferred from Buffer" event with the NI USB-9263 but receive the following error message when I try to run the code: Error -200980 Possible reason(s): Measurements: DAQmx Every N Samples Transferred from Buffer Event is not supported by the channel types or devices in your task. Why am I receiving this error? Solution: The NI USB-9263 is a NI-9263 module in a USB-9162 carrier. The USB-9162 lacks the onboard FIFO used with the NI-9263 module in other platforms and thus does not support this event. A workaround will be to use alternative programming loops. Related Links: NI 9263 Operating Instructions and Specifications Attachments:
Report Date: 03/25/2008 Last Updated: 08/14/2008 Document ID: 4JODJ6QA |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||