Problem:
I am trying to configure the IP settings on my FieldPoint embedded controller. Upon rebooting the controller to enable the new settings, the Status light now blinks four times.

Solution:
This behavior can occur when one specifies an incorrect default gateway when configuring the Network Settings of the FieldPoint controller in Measurement and Automation Explorer.

The default gateway is what links the host's subnet to other networks. As such, if one specifies an incorrect default gateway, the host might not be able to communicate with targets on remote networks. Specifically, if a single physical network has more than one router (for example, one router is configured for an internal TCP/IP network and another router is connected to the Internet), one must ensure that the internal network router is assigned as the default gateway.

Moreover, because the default gateway is what links the host to destinations on other remote networks, it is imperative that the host and default gateway are located on the same subnet.

For more discussion regarding the basics of TCP/IP addressing, visit Microsoft's KnowledgeBase on Understanding TCP/IP Addressing and Subnetting Basics.

Related Links:
Microsoft Help and Support: Understanding TCP/IP addressing and subnetting basics
KnowledgeBase 2FF6N4KN: Choosing an IP Address for Your Real-Time Engine

Attachments:





Report Date: 05/03/2007
Last Updated: 09/01/2007
Document ID: 492IRP3N

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5
Please Contact NI for all product and support inquiries.submit