Why Do I Receive DAQmx Error -200488 When Running a Task Saved in My Project Primary Software: LabVIEW Development Systems>>Full Development SystemPrimary Software Version: 8.0 Primary Software Fixed Version: 8.2 Secondary Software: Driver Software>>NI-DAQmx
Problem: I am using LabVIEW 8.0. If I create a new DAQmx task in the project manager that has more than 10 channels, it gives me Error -200488 occurred at DAQ Assistant. This occurs when I create the task, save the project, close LabVIEW, reopen LabVIEW, and run the task. Solution: There was a bug in LabVIEW 8.0 that caused tasks saved in the project to only save the first 10 channels. To get around this you can create your tasks in Measurement or Automation Explorer or programmatically in your LabVIEW VI. Related Links: NI Developer Zone: Creating a Task in NI-DAQmx and Using it in LabVIEW Attachments:
Report Date: 01/30/2008 Last Updated: 02/11/2008 Document ID: 4HTCQK0R |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||