Querying Lookout 3.8 Data after Upgrading to Lookout 4.0 (or Higher)

Primary Software: Lookout
Primary Software Version: 4.0
Primary Software Fixed Version: N/A
Secondary Software: Utility Software>>Citadel ODBC Driver

Problem: After upgrading to Lookout 4.0 (or higher), querying data created with Lookout 3.8 via Microsoft Query will return:
    "Unable to connect to data source: Data path="c:\temp\database" Drivers_SQL_Set_Connect_ATTR, The driver returned invalid ( or failed to return ) SQL_Driver_ODBC_VER:%s"
or a similar error.

Solution: This error is due to the fact that the ODBC driver has been updated since Lookout 3.8 build 16. To be able to query data created with Lookout 3.8 build 16 (or older), you must install the National Instruments 32-bit Citadel Database. Both versions of the ODBC driver may coexist on the same machine.

You may download the appropriate version of the ODBC driver from our our Drivers and Updates database (see the related link, below).

Related Links: Drivers and Updates: Citadel 3.8 ODBC Driver

Attachments:





Report Date: 05/16/2001