Why Do I Get Error 88716 When I Perform Self Test on My DAQ Device on My Real-Time (RT) Controller?Primary Software: LabVIEW Modules>>LabVIEW Real-Time ModulePrimary Software Version: 8.6.1 Primary Software Fixed Version: N/A Secondary Software: Driver Software>>NI-DAQ, Driver Software>>NI-DAQmx
Problem: I have installed a data acquisition (DAQ) device on my RT target (such as an RT PXI Controller or a PC converted to a RT target). When I perform self test on my DAQ devices installed on my RT target, I get the following error: Error -88716 occurred at Self Test.Possible Reason(s): The requested operation failed because the versions of a driver installed on the local and the remote system are different. Update the driver so the versions on the two systems are the same. ![]() How do I fix this? Solution: The error is due to a mismatch in the DAQmx (or Traditional DAQ) driver versions. To fix the problem make sure you have the exact same version of the driver on the RT target and on your host computer.
Related Links: Drivers and Updates: DAQmx Attachments:
Report Date: 04/02/2007 Last Updated: 10/16/2009 Document ID: 481AH2LA |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||