Academic Company Events NI Developer Zone Support Solutions Products & Services Contact NI MyNI
3 ratings:
 2.33 out of 5     Rate this Document

Why Do I Get Error 88716 When I Perform Self Test on my DAQ Device on my Real-Time Controller?

Primary Software: LabVIEW Modules>>Real-Time Module
Primary Software Version: 6.0
Primary Software Fixed Version: N/A
Secondary Software: Driver Software>>NI-DAQ, Driver Software>>NI-DAQmx

Problem:
I have installed a data acquistion (DAQ) device on my Real-Time target (such as a RT PXI Controller or a PC converted to a Real-Time target). When I perform self test on my DAQ devices installed on my RT target, I get the following error:

Error -88716 occured at Self Test.



How do I fix this?

Solution:
The error is due to a mismatch in the DAQmx (or DAQ) driver versions. To fix the problem make sure you have the exact same version of the driver on the RT target and on your host computer.
  1. Find your RT target under Remote Systems in the Measurement & Automation Explorer (MAX)
  2. Click on the "+" sign next to the name of your RT target to show all folders that belong to your RT target.
  3. Right-click on the Software folder and select Add/Remove Software
  4. Find the DAQmx (or Traditional DAQ) driver in the list of Real-Time software and make sure the version on the host PC matches the version on the RT target.
Note: Even though here we use the DAQmx driver as an example, you will get the same message for any device (for example a serial device) whose driver versions are different on the host PC and on the RT target.

Related Links:
Drivers and Updates: DAQmx

Attachments:


Error88716.jpg - Error88716.jpg



Report Date: 04/02/2007
Last Updated: 05/27/2009
Document ID: 481AH2LA

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
  1 2 3 4 5
Please Contact NI for all product and support inquiries.submit