Can a cFP-CTR-502 Module Measure a 50 kHz Signal?Hardware: PXI/CompactPCI>>Controllers
Problem: I would like to sample a 50 kHz signal with my cFP-CTR-502 module, but the internal frequency references are 1 kHz and 32 kHz. Solution: The cFP-CTR-502 module can measure pulses up to 50 kHz. The only requirement for doing this is that the minimum pulse width is 10 microseconds. The 1 kHz and 32 kHz internal time bases are only used for generating pulses internally to be counted. The KnowledgeBase referenced in the Related Links section, How Do I Connect Two Sinking I/O or Two Sourcing I/O Together?, can be referenced to see how to connect a sourcing output to a sourcing input so that you can use the cFP-CTR-502 for measuring a 50 kHz signal. Related Links: KnowledgeBase 2K0D6H5F: How Do I Connect Two Sinking I/O or Two Sourcing I/O Together? KnowledgeBase 3ARE14GP: How Does the FieldPoint Frequency Measurement Shipping Example Work? Attachments:
Report Date: 12/07/2007 Last Updated: 03/13/2009 Document ID: 4G6G64ES |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||