Do I Need to Purchase IA OPC Server to Work With LabVIEW DSC if I Already Have Lookout?
Primary Software: LabVIEW Modules>>DSC Module
Primary Software Version: 7.1
Primary Software Fixed Version: N/A
Secondary Software: Lookout
Problem: I recently purchased LabVIEW DSC to take advantages of the its programming capabilities. I need to communicate with my PLC which I was able to do earlier with Lookout. Can I still use Lookout as the OPC Server or do I need to purchase IA OPC?
Solution: - You do not need to purchase IA OPC to act as an OPC Server. You can use Lookout as easily. To do so follow these steps:
- Open Lookout and create a new process
- Add your PLC driver object to this process and configure it. Once this is done, deploy the process
- Now, open LabVIEW and add a numeric control to it
- Right click on the control and choose Data Operations>DataSocket Connection...
- Click on 'Browse' and choose to 'Browse Measurement Data'
- Under 'My Computer' click on 'National Instruments.LookoutOPCServer'
- You should now see your process listed along with the objects (including the object communicating with your PLC) that are running within that process
- Bind the control to the appropriate data member list under the PLC Driver Object
Related Links:
Attachments:
Report Date: 11/14/2005
Last Updated: 12/19/2005
Document ID: 3RDG886K