Why Does My [c]FP-CTR-50x Module Miss Pulses?Hardware: FieldPoint>>Discrete I/O Modules>>FP-CTR-500, FieldPoint>>Discrete I/O Modules>>FP-CTR-502, Compact FieldPoint>>Discrete I/O Modules>>cFP-CTR-500, Compact FieldPoint>>Discrete I/O Modules>>cFP-CTR-502
Problem: Why does my [c]FP-CTR-50x counter module fail to count the first few pulses of my source signal? Solution: This is a known issue that affects the following revisions of the [c]FP-CTR-50x counter module:
While configured to the 50 kHz filter setting, these modules may fail to count a few source signal pulses under two conditions. The details are in the table below.
To work around these problems, leave your counters configured to the 200 Hz filter setting (i.e. do not change the setting on the fly while acquiring data), or if you must use the 50 kHz filter setting, ensure that the inputs do not remain idle for more than 25 minutes. Please accept our apology for the inconvenience. National Instruments is committed to your total satisfaction and to maintaining your confidence in our products. If you have any technical questions or concerns, please call 1-877-493-2406 and ask to speak with an Applications Engineer. Related Links: KnowledgeBase 3KEAE473: (c)FP-CTR-500 Destroyed When Applying External Power KnowledgeBase 3V2EL1IH: [c]FP-CTR-50x External Power Supply Voltage Specification is Incorrect Attachments:
Report Date: 02/27/2006 Last Updated: 09/15/2006 Document ID: 3TBGIBPT |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||